INC Products > Industrial Modbus I/O Modules > Analog Input / Output |
|
|
| |
 |
| |
| Introduction |
SUNIX ioSCADA SM series is a series of industrial Modbus I/O. It supports standard
Modbus (RTU & ASCII) protocol. Type of SUNIX ioSCADA modules include Digital
Input, Digital Output, Analog Input, Analog Output and Counter/Frequency Input
meet with most industrial automation applications. SUNIX ioSCADA series are
different to traditional I/O modules used in laboratory, SUNIX ioSCADA offers
great performance in Electric Power Plant, Steel Manufacturer and Petrochemical
Plant, which are harsh environment and require high immunity against noise,
more efficient, real-time response, long MTBF (Mean Time Between Failure), high
reliability and excellent measure precision. SUNIX ioSCADA are ideal for DCS, PLC
and SCADA system applications.SUNIX ioSCADA within convenience DIP Switch
for setting RS-485 ID address and Serial parameters , no need to configure by any
utility software. The modules are also embedded with RS-485 terminator. The RS485 network support 4,000 feet without network repeater.
The compact design enables DIN Rail installation. The slide-in cover design that helps user to keep track of the I/O structure. SUNIX
ioSCADA SM series not only for Data Acquisition but also include special control function such as I-to-O, ON/OFF Latch, Max./Min.
Lock, ON/OFF Delay Timer, TCP Control and Ramp Control in order to coordinate with SCADA system.
The ioSCADA modules work as independent controller while offering the data collection and control functions. Hence making
them perfect choice for SCADA & DCS applications at the industrial grade environments. |
|
|
|
| ioSCADA Common Specifications |
| Communiction Interface |
| Protocol |
Modbus-RTU/ASCII protocol, RS-485 (3-Wire) |
| Baud Rate |
1200, 2400, 4800, 9600, 19.2k, 57.6k or 115.2k baud |
| Module Addressing |
1 ~ 63, selectabe. Default address 1 |
| Network Distance |
4000 feet without network repeater |
| Max Nodes |
Nodes Supports up to 63 modules without the use of a network repeater |
| Frame |
Data Bits 8 Parity none, Stop Bits 1 |
| Watchdog |
Communication Failure |
| Network Isolation Voltage |
3000 Vrms |
| Over Voltage Protection |
70 VDC/VP-P |
|
|
|
|
|
|
|
| Supported Modbus Commands |
| Function Code |
Description |
| 1 |
Read Coil (Output) Status (0x) |
| 2 |
Read Input Status (1x) |
| 4 |
Read Input Registers (3x) |
| 3 |
Read Holding Registers (4x) |
| 5 |
Force Single Coil (Output) (0x) |
| 6 |
Present Single Register (4x) |
| 8 |
Loopback Command |
| 15 |
Force Multiple Coil (Output) (0x) |
| 16 |
Preset Multiple Registers (4x) |
| 17 |
Report Slave ID |
| |
Command Exception support |
| |
Broadcast Command support |
|
| Isolation Voltage |
RS-485 Isolation |
3000 Vrms |
| Field Side to Logic Side Isolation Voltage |
3000/5000 Vrms (Analog/Digital) |
| Channel-to-channel Isolation |
Yes |
|
| Environment |
Operating Temperature |
-30 ~ 75 ℃ |
| Storage Temperature |
-45 ~ 85 ℃ |
| Relative Humidity |
5 ~ 90%, Noncondensing |
|
| Electromagnetic Compatibility |
| Electrical Fast Transient Immunity (EFT) |
IEC61000-4-4 level 3 (Power, Signal lines) |
| Electrostatic Discharge (ESD) Immunity |
IEC61000-4-2 Level 3/2 (8KV/4KV air/direct discharge) |
| Surge Immunity |
IEC61000-4-5 (0.5KV COMM.) |
|
|
|
|
| |
| SM_UI_108i Specifications |
|
|
|
|
|
|
| Specification |
| Productl Description |
8 Channels Universal Analog Input Module |
| Input Channels |
8, Differential |
| Input Range |
± 20mA, 4 to 20mA, ±10V, ± 5V, 1 to 5V
±100mv, ±500mV
Thermocouple Sensor Types : J / K / T / R / S / E / B / N |
| Input Accuracy |
( @ 25℃ ) ± 0.05% of input range (a / v/ mA) |
| Resolution |
Thermocouple input : 0.1℃ (0.18℉), others 16bit (1 part in 32,000) |
| Ambient Temperature Effect |
Better than ±0.005% of input span per ℃, or ±1.0µV/ ℃, whichever is greater |
| Noise Filter |
50 / 60Hz Auto |
| Noise Rejection |
Normal mode : 60dB @ 60Hz, typical
Common mode : 88dB @ 60Hz, typical |
| Input Filter Bandwidth |
-3dB @ 1.5Hz , typical |
| Input Conversion Rate |
140ms (per channel) |
| Current Input Resistance |
250 Ω |
| Voltage Input Impedance |
100K Ω |
Over Voltage Protection
(Voltage Inputs Only) |
60 VAC |
Over Current Protection
(Current Inputs Only) |
300 mA |
| External cold-junction compensation |
Yes |
| Thermocouple Break Detection |
Yes |
| TC Input impedance |
20 M Ω |
30
| TC Input bias current (break) |
200 µA typical |
| TC Pvervoltage Protection |
±15V |
| Reference-junction Accuracy |
0.15℃@0 ~ 70℃ , 0.5℃@ -20 ~ 0 ℃ |
| Watch Dog |
Hardware |
| Power Requirements |
10 ~ 30VDC |
| Wiring |
I/O Cable 16 ~ 24AWG |
|
| Analog Input Function Block |
| Offset adjust |
-128 ~ 127 |
| Input Smoothing |
1 ~ 255 |
| Latch Max. Value |
Yes |
| Latch Min. Value |
Yes |
| High/Low Alarm |
Yes |
| Over/Under Range Alarm |
Yes |
| Over/Under Flow Alarm |
Yes |
| Break Alarm |
Yes |
|
| Input Range & Accuracy |
TC |
℃ Range ( °F Range ) |
Accuracy |
J |
-210 ~ 1200 ℃ (-346 ~ 1712 °F) |
± 0.1 ℃ |
K |
-200 ~ 1372 ℃ (-328 ~ 2502 °F) |
± 0.1 ℃ |
T |
-260 ~ 400 ℃ (-436 ~ 752 °F) |
± 0.1 ℃ |
R |
-50 ~ 1768 ℃ (-58 ~ 3214 °F) |
± 0.3 ℃ |
S |
-50 ~ 1768 ℃ (-58 ~ 3214 °F) |
± 0.5 ℃ |
E |
-200 ~ 1000 ℃ (-328 ~ 1832 °F) |
± 0.1 ℃ |
B |
-260 ~ 1820 ℃ (-500 ~ 3308°F) |
± 0.5 ℃ |
N |
-230 ~ 1300 ℃ (-382 ~ 2372 °F) |
± 0.1 ℃ |
|
|
|
|
|
|
|
|
|